Installation Sheet
Panel Mount
Rev. 052115
HAC Series
AC Load Solid State Contactors
FEATURES
PART NUMBER NOMENCLATURE
The HAC Series Solid State Contactors (SSCs) are designed for control of high power AC loads
such as heaters, motors, lights, pumps, solenoids, transformers, etc., where long life and
reliable AC switching are required and traditional mechanical contactors or relays don't provide
the required life, performance or service levels. The HAC Series offers the latest in AC Solid
State Power control by virtue of Crydom's proven AC power switching technology and control
circuitry. Advanced thermal design provides superior performance for loads rated up to 150
Amps rms from 48 to 660 VAC.
150 Amp AC Load Ratings @ 40ºC ambient with 0.25ºC/W heat sink
Single Pole Single Throw Normally Open operation (SPST/N.O.)
LED Input Status indicator standard
UL & cUL recognized
Required for valid part number
For options only and not required for valid part number
(A) See compatible accessories in TABLE 1.
(B) For maximum ratings use heat sink ratings shown in HAC series derating curves (see product
datasheet).
(C) Load can be wired to either terminal L1 or terminal L2.
MOUNTING INSTRUCTIONS
Mounting on Heat Sink
Mounting on Panel
Please read all installation instructions before using your HAC Series Solid State Contactor (SSC).
Choose one of the two mounting options and follow the instructions.
Locate the panel section on which the HAC Series SSC will be mounted. Panel mount
surface must be clean, bare metal and provide adequate heat sinking capability. (B)
Be sure to use thermal pad or thermal compound between the SSC and the panel.
HAC Series Contactor mounting slots have a diameter of 0.2 in (5.0 mm). Four screws are
needed (not included) to mount the SSC onto panel. Choose screw length considering the
mounting surface and that HAC Series baseplate thickness is 0.125 in (3.2 mm).
Before applying full torque, tighten down all 4 screws until they contact the baseplate.
Then, tighten them to 20 in-lbs (2.2 Nm) starting with one immediately followed by the one
in the diagonally opposite corner. After the first 2 screws are completely tightened,
proceed tightening the remaining 2 screws.
Select adequate heat sink (see thermal derating curves).
Be sure to use thermal pad or thermal compound
between the SSC and the selected heat sink.
HAC Series Contactor mounting slots have a diameter of
0.2 in (5.0 mm). Four screws are needed (not included) to
mount the SSC onto heat sink (See fig. 1). Choose screw
length considering the mounting surface and that HAC
Series baseplate thickness is 0.125 in (3.2 mm).
Before applying full torque, tighten down all 4 screws
until they contact the baseplate. Then, tighten them to 20
in-lbs (2.2 Nm) starting with one immediately followed by
the one in the diagonally opposite corner. After the first 2
screws are completely tightened, proceed tightening the
remaining 2 screws.
fig. 1 HAC Series SSC
mounted on HS053 heat sink
(A)
(A)
For optimal thermal performance heat sink fins should be oriented vertically to promote
natural airflow.
(B)
Thermal pad
WIRING DIAGRAM
Series
Operating Voltage
24: 24-280 VAC
60: 48-660 VAC
Control Voltage
A: 150-270 VAC
B: 90-140 VAC
D: 4-32 VDC
Rated Load Current
150: 150 Amps
A24 150
Thermal Pad
Blank: Not Included
H: Included
HAC
Overvoltage Protection
Blank: Not Included
P: Included
P
Switching Type
Blank:
Zero Voltage Turn-On
-10: Instantaneous Turn-On
-10H
Wire Size
Maximum wire size capacity: Input 12 AWG (3.31 mm
2
) through suggested
mating connector (see TABLE 2), Output 2/0 AWG (67.4 mm
2
).
Connections
First install Lug Terminal (Item 1 on fig.2) followed by Washer Int. Tooth-Lock
(Item 2 on fig.2) and finally Nut Hex (Item 3 on fig.2)
Terminals
For maximum ratings, for 150 Amp models use Crydom lug terminal TRM3/0 or
other lug terminal with a diameter of 0.375 in (9.52 mm), 2/0 AWG (67.4 mm
2
) 75ºC
insulation wire installing capable.
Important Considerations
WARNING! Do not try to unscrew Terminal Studs from Product.
Be sure to use input and output voltages within operating ranges.
LED indicates only input status. It does not represent output status.
Hardware Kit
TABLE 1. Accessories
Thermal Resistance
[ºC/W]
Heat Sink
Part No.
0.5
0.36
0.25
HS053
HS033
HS023
HK1 TRM3/0
Thermal Pad
HSP-3
HSP-5
Lug Terminal
3
2
1
fig. 2 Lug Terminal
Connections
(C)
HAC60D150
4-32 VDC
INPUT
STATUS
L1
L2
LOAD SIDE
SOLID STATE CONTACTOR
AC
Load
V
(
-
/ ) (+ / )
L2 ( ) L1 ( )
TABLE 2. Suggested Mating Connectors/Plugs
Front Wire Entry
Molex: 0395332002
Phoenix: MVSTBW 2,5/ 2 -ST-5,08
Right Angle
Molex: 0395300002
Phoenix: MSTB 2,5/ 2 -ST-5,08
Rear Wire Entry
Molex: 39533 -3002
Phoenix: MVSTBR 2,5/ 2 -ST-5,08