DIN rail or panel mount 90 mm (width) package
Box Clamp terminals
Bracket fits all standard 35 mm DIN rail profiles
LED input status indicator
FEATURES
Crydom CTR Series Solid State Relays were developed to offer the advantages of semiconductor
switching technology in a compact, self contained package. Quick and easy installation is
coupled with low drive power requirements and efficient, reliable power SCR output.
IMPORTANT CONSIDERATIONS
Mounting air gap
(A)
Earth Bonding (Grounding)
To achieve maximum ratings if multiple units are installed, there must be a minimum air gap of 0.8 in (20
mm) between the devices (horizontally) and of 3.15 in (80 mm) measured between DIN clip tabs
(vertically).
The CTR heat sink is equiped with an earth bonding screw as is required for Class 1 Protection, in
accordance with EN 60950 (VDE 0804). Recommended torque is 20 in-lbs (2.2 Nm).
DIN Rail Mountable SSRs Three-Phase
CTR Series
MOUNTING INSTRUCTIONS
Mounting on DIN Rail
Mounting on Panel
Please read all installation instructions before using CTR Series SSRs.
Choose one of the two mounting options and follow the instructions below.
Locate the panel section on which the CTR SSR will be mounted on.
DIN clip includes tabs for this type of mounting. Tab holes have a
diameter of 4.5 mm. You will need two screws (not included) no
larger than that to mount the SSR onto panel.
Align SSR tabs with panel surface and screw both top and bottom
sides. Recommended torque is 12 in-lbs (1.36 Nm).
Locate rail and align with non moveable end of CTR DIN clip.
Using reasonable force, push CTR in the direction of the arrow
shown in fig.1.
For removal pull release tag in direction of arrow using blade of
screwdriver and pull it away from DIN rail.
To install
on DIN rail
To remove from DIN rail
fig.1 Mounting on DIN Rail
PART NUMBER NOMENCLATURE
Required for valid part number
For options only and not required for valid part number
CTR 25 -1060D
Series
Operational Current
25: 25 Amps / Phase
Control Voltage
B: 90-140 VAC
C: 180-280 VAC
D: 4-32 VDC
Operational Voltage
60: 48-600 VAC
Switching Mode
Blank: Zero Voltage Turn-On
-10: Random Turn-On
(DC Control only)
(A)
(B)
(C)
The air gap is the clearance distance adjacent to either side of the relay or assembly measured to
the next closer relay or assembly.
CTRCxxxx is rated at 60ºC max. ambient.
100% Duty Cycle.
Rev: 062411
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Custom Sensors & Technologies. Specifications subject to change without notice.
Installation Sheet
DIN Rail Mount
Page view 0
1 2

Summary of Contents

Page 1 - Installation Sheet

DIN rail or panel mount 90 mm (width) packageBox Clamp terminalsBracket fits all standard 35 mm DIN rail profilesLED input status indicatorFEATURESCry

Page 2

The following deating curves must be observed before installation.DERATING CURVES(B, C)Load Current (Amps)30252015105020 40 6080Ambient Temperature (º